An Experimentak study into the effect of fin spacings and working fluids on the performance of a heat pipe-heat exchanger /
المؤلف
Ahmed, Usama Abdalla Mostafa.
هيئة الاعداد
باحث / اسامة عبدالله مصطفى احمد
مشرف / محمد فائق عبد ربة
مناقش / رمضان محمد عبد العزيز
مناقش / محمد حسن صقر
الموضوع
Pipe-heat exchanger.
تاريخ النشر
1996.
عدد الصفحات
114 P. :
اللغة
الإنجليزية
الدرجة
ماجستير
التخصص
الهندسة الميكانيكية
تاريخ الإجازة
1/1/1996
مكان الإجازة
جامعة بنها - كلية الهندسة بشبرا - Department ofmechanic
الفهرس
Only 14 pages are availabe for public view

from 133

from 133

Abstract

In this work the effect of fin spacing and type of working fluid on the performance characteristics of a counter flow heat pipe-heat exchanger is investigated.
A test apparatus is designed and constructed to achieve heat transfer measurements from six tested fin spacing resulted from externally aluminum finned gravity - assisted heat pipes.
These pipes are arranged in staggered form constituting three rows (6-5-6) R22, R12 and Acetone are used as the working fluids for these pipes
The evaporator and condenser sections of the heat transfer elements are facing the counter - flowing air streams at different operating temperateres.
This atudy is first carried out on bare pipe and finally on the exernally finned pipes usinggggg a 0.3mm aluminum sheet fins with 2mm, 4mm, 6mm, 8mm and 10mm fin spacing.
A detailed analysis of the experimental results ensures that both the heat pipe-heat exchanger effectiveness and the (NTU) is greatly affected by the number of fins in one centimeter.
Also , the overall heat transfer coefficient and the overall conductance of the heat exchanger showed a significant dependence on the heat pipes arragement.
The experimental results showed that:-
1-The heat pipe-heat exchanger effectiveness increases with the decrease in fin spacing while keeping the evaporator temperature constant, an improvement with 5 fin/cm of four times over that of bare pipe.
2-The (NTU) is directly proportional to the number of fins in one centimeter.
3-The overall heat transfer coefficient of the heat exchanger increases as the number of fins in one centimter increases.
4-The overall heat transfer coefficient of the unit increases as Reynolds number on the evaporator side (Reh)
increases.
5-The overall conductance (Q/Atm)of the heat exchanger increases as Reynolds number ratio (R*e)increases.
6-The type of the working fluid filling the heat transfer elements, has a pronounced effect on the effectiveness and the capacity of the heat exchanger. Using R22 achieves an improvement in the effectiveness over 150%than Acetone .
7-from the present result, it is advised to use heat exchangers with staggered heat tr ansfer elements equipped with fins of 5 fin/cm to improve its performance characteristics.